Most downtime I've seen in datacenters has been due to irregular power, not power loss. Case in point.
Dummy loads are good for testing but they are not typically variable - if you had 2.5mva generators and a 1mw dummy load you wouldn't be able to run more than 1mw of critical IT load.
I'll say this is the first I've heard of not having enough load to start a generator. They will happily start up and idle.