Unlikely.
> but it's likely that gas main pressure is controlled by a computer.
But the failsafes are not. Overpressure is something the system is designed to handle, and those gas substations that you see every now and then in fields are the places where the overpressure regulation devices are located, and they are purely mechanical.
> It'd be shocking if a software failure could cause dozens of fires.
It would be, but this isn't that. The actuators on these systems are made with the express purpose that line fluctuations will always be slow enough to catch up with. But if a regulator fails in a bad way that might cause a prolonged overpressure with the initial change arriving as a spike, which may expose further weaknesses downstream.
So the signature of an upstream regulator failure (a big one, and a sudden one too), is fairly consistent with what you are seeing here. The software actuators would not cause a pressure rise fast enough for that initial spike and the limit settings on those actuators (which are mechanical) would not allow those actuators to move beyond certain minimum and maximum set points for each line that they service.
The people that designed these systems were anything but stupid and it is failsafes layered on more failsafes, the big killer for systems like this is a very simple one: back maintenance.
Your comment seems to be implying that there is some sort of evidence of hacking here, which, unless I'm missing something, does not seem to be the case.
A gas explosion (claimed to be among the biggest non-nuclear explosions) was caused by the CIA hacking a soviet pipeline: https://www.telegraph.co.uk/news/worldnews/northamerica/usa/...
No idea what caused today's explosion, but the USA is clearly not without enemies and vulnerabilities in its own infrastructure.
Yet its also too destructive and attention seeking to be a plausible threat or sending a message; if outsiders messed with the SCADA to do this, fifteen minutes later all the passwords would be changed and sites physically locked down, such that a threat to do something more destructive next time (or else..) such as flicking the gas supply off for a couple minutes would be a non-starter. You have to look at it militarily like a stealth attack; giving away your position is not a wise first move if your whole strategy is stealth. You get one shot and this would be an intentional miss, so ...
This would also imply its not an inside job; an insider would know that in my state (admittedly not MA, thankfully) an interruption in pressure requires an attempt at physical access by a rep with a leak sensor to verify pilot light and pilot light safety interlock for EVERY point of use and/or door tag notification warnings. Its happened to me a couple of times for some street work replacing pipes and replacement of my old meter. Its kind of an expensive labor job, a wealth transfer from the company to the union. The fact this didn't happen kind of exonerates the union.
So rule out outsiders and insiders. A nutjob would probably drive a truck into an above ground facility, or frankly, just drive into people, so its probably not a nut. Not many options left. Space aliens did it accidentally? Maybe they closed down that solar observatory in NM because the space aliens are coming to mess with our delicious natgas.
https://en.wikipedia.org/wiki/Pressure_regulator
...and the cause may be as simple as the regulator valve sticking open for some reason.
Let’s put it this way: it wouldn’t surprise me, especially in Lawrence, if some of the gas mains were still made out of wood. Before you scoff, NYC replaced the last wood gas main that they knew of 25 years ago, but they still occasionally find wooden pipe in their systems.
The best way I’ve heard the gas infrastructure described is “antiquated ... if it was aged, it could be updated and replaced, but it’s so antiquated all that can be done is patchwork because there’s no time to do anything but.”
https://www.politifact.com/truth-o-meter/statements/2010/sep...