>It transfers high levels of power over non-power cable
You can't beat physics. Wires heat up from current, regardless of whether it's AC, DC, or "digital" pulsed DC. I doubt Ethernet cable is rated for any significant amount of power, but searching for "cat6 max power" doesn't return any relevant results because search is broken in 2019.
It's also likely to be rather inneffecient, as they are converting from AC to DC and then potentially back to AC? There may be an advantage to pulsing DC but I'm not sure, typically AC is more efficient for power transmission because of lower losses for the same power over distance and higher transformer efficiency (no need for an inverter).
Normally, running high voltage through a wire is dangerous because a fault can dump power into the middle of the wire (starting a fire) or into a person (stopping their heart), but perhaps with end-to-end active monitoring, it's possible to operate safely at much higher voltages?
If this technology works, I think it would also be useful for powering a tethered drone from the ground.
[Edit: according to lopmotr's link, they are using this for drones and balloons already.]
[1] http://magazine.connectedremag.com/publication/?i=488126#{%2...
I think this is a pretty nice idea except for the patents and only having one or two suppliers and lack of technical details.
No idea how this would be more efficient. Bursting voltage will lead to higher loses versus a continuous voltage. Are they claiming efficiency thanks to a centralized AC->DC converter?
That said...Belden is reputable, but this doesn't sound like it's fully baked.
CAT6 cabling uses 4 pairs of AWG 24 wire. This type of wire typically comes with two options for insulation 250V and 600V, Let's be optimistic and use the latter. The maximum recommended current for AWG 24 wiring is 0.577A [1], as a reference PoE specs use 0.3A (if I remember correctly). Using these assumptions our maximum power transmission would be 4 (pairs of wire) * 600V * 0.577A = 1384.8W, this doesn't include power losses inside the wire itself. Belden's descriptions seem to indicate that power transmission is multiplexed in the time domain, which would reduce the power transmission capability even further.
Current limits on wiring are semi-arbitrary, what it really comes down to is how much heat generation is tolerable in the wires and the environment in which they reside. If we were to ignore the suggested current limit of 0.577A per core then it is possible to transmit 2000W. More specifically you would need 0.833A at 600V in 4 pairs of wire to get 2000W.
TLDR: The claims seem dubious. It is possible if the current limits for AWG 24 wire are are exceeded by about 2x.
The other advantage it that solves a lot of the IoT last 25 feet problem. Because it's both power and a data link.
[1] https://www.belden.com/products/enterprise/copper/cable/de-c...
4 * 300V * 2.3A = 2.76kW
It looks like it's totally doable with those cables! But if they're running 300V DC through there... may as well just run 120Vac. The only benefit I see is that they can detect faults on the transmitting end in a sophisticated manner.