* no emergency electricity cut-off device, an "economic strategy choice of the site operator" - the electrical room where the fire started was hot, 400C at the door (measured by thermal camera), with meter long electrical arcing from the door, thundering deafening sounds. Making access of utility technicians "difficult" - it took them 2 hours to cut incoming electrical service from the utility. On site UPS devices also had no cut-off, so they kept supplying.
* emergency water network provided only 70m3/h at the site. A firefighting boat arrived, Europa 1, was called, supplying 14.5m3/min max flow rate.
The freeflowing air cooling design, a good design choice as it saves on operating costs for cooling, contributed to nourishing the fire.