In '86, I was in a data center that had expanded to take up 70% more space. During the expansion, emergency lighting hadn't been put up. During expansion, a 470 volt three-phase line had been put in, the insulation had been stripped off while they were pulling it through the conduit. As it heated up, gas or vapors from the melted insulation built up and the 1/4" thick conduit was ripped open with roughly an 8" hole and an explosion people on the first floor heard (computer room was in the basement).
One of the operators panicked, tripped over the anti static carpet, ripped the Fire Suppression box off the wall and pulled the Halon. He stumbled out the automatic sliding glass doors and hit the EPO leaving the data center completely dark with me about 120' from the door in pitch black.
I had walked those corridors between the drives hundreds of times, but, had difficulty finding the path. Time was running out, so, I stood on one of the minicomputers, moved one of the drop ceiling tiles and stuck my head into the return air plenum and the Halon went off. It was noisy, sort of a giant whoosh with a low rumble and a very odd smell.
I don't know how long I stood there, but, it wasn't more than a few minutes before a flashlight was shining on me with a Fireman in full gear.
After that, we had emergency lighting and oxygen tanks throughout and the Halon system was upgraded. When the tanks were refilled, they did the math and noticed that the amount of Halon we had wasn't enough for the expanded data center and probably wouldn't have extinguished a fire.
Most humorous moment - seeing firemen walk through the data center with axes in hand looking for fire.