It's not about getting the generator to spin at 50hz, it's about getting it to spin at 50hz under dynamic load. Most generators are mostly fixed speed I think for the sake of efficiency, so the mechanism the grid has to regulate the frequency of power is largely by controlling the number of generators running at any given time, and how much of the grid is connected to them. Ramping up and down based on the current observed frequency of the grid is exactly how this all works. However it's more complicated because what if two or more power stations see a low frequency grid and decide to ramp up more generators? Well now the grid frequency is too high. If they them respond to that by ramping down, it'll go too low. Rinse and repeat and you get undesirable frequency oscillation, so there needs to be more communication across the grid than just responding to the locally observed frequency.
Connect a stopped, or sufficiently out of phase generator to a full scale power grid and the puny thousands of pounds of metal that make up a generator are going to get ripped apart by the sheer inertia of the power grid forcing it to match speed and phase in an instant. This is also a problem when attempting to connect two isolated grids, of they're too out of phase with each other, catastrophic physical damage will occur.