I was just reading about the Fukushima accident, and how most of the EDG's failed because they were water-cooled, and while the EDG's were located out of harms way, the pumps for providing cooling water were located on low ground and were damaged by the tsunami. http://fukushima.ans.org/report/accident-analysis
Yesterday I saw a story about the Datagram data center in NYC having to shut down. From their reports about the damage (http://www.datagram.com):
"As of 5pm on October 29, 2012, Datagram had thoroughly tested its emergency systems at 33 Whitehall, NYC fully staffed and awaiting the storm to hit Manhattan's shores. Once ConEd lost power to Lower Manhattan, Datagram's emergency systems kicked on maintaining power to Datagram's datacenter. Unfortunately, within a couple hours of the storm hitting Manhattan's shores, the building's entire basement, which houses the building's fuel tank pumps and sump pumps, was completely filled with water and a few feet into the lobby. Due to electrical systems being underwater the building was forced to shut down to avoid fire and permanent damage."
It's pretty obvious that, despite all the disaster planning done in the past, Datagram (and TEPCO, and others) have really neglected to appreciate the potential modes of failure for their backup power systems. In both cases, they misunderstood the threat to critical backup power infrastructure. If your EDG is on the roof but the fuel pumps and electrical switchgear is in the basement, what will happen during a flood? If your EDG's are on high ground but the pumps to cool them are not, what happens during a tsunami?