Your circuit breaker protects your circuits by putting all the load (eg your microwave) on one side, and your supply (mains power) on the other. If too much load is present, the circuit breaker trips.
However, plugin solar puts invisible supply on the load side, which your circuit breaker cannot see. Let's make an absurd example so you can see what the problem is, then scale it back.
Imagine someone buys 5 panels that can each supply 5amps. They plug them into outlets on a 40 amp circuit. They then proceed to run their toaster, microwave, vacuum, and hair dryer. They can draw 65 amps through the wires before the circuit breaker trips. (40 from mains, 25 from the panels)
Let's say they had a good electrician who installed 6AWG wiring on that circuit, which is rated for 50 amps. The circuit breaker used to trip at 40, so no problem. But now up to 65 can go across the wires and suddenly you are exceeding rating for wires.
Now you might say, "most of these are 3.5 watts, and they clearly say don't use more than one". But I say that's a "good intentions solution". We should make it mechanically impossible to do the wrong thing. Maybe these panels could try to communicate over the electrical wires, and if they detect a signal from another panel they should self limit. Maybe we need to rethink circuit panel design. But as it stands people will absolutely buy one of these, decide they love it, and then buy 4 more.