Everything serious in the telecom/ISP infrastructure sector has a big -48VDC battery plant, or preferably separate A and B side -48VDC battery plants, to provide a significant buffer between power going Grid --> AC-to-DC Rectifiers --> Equipment, and when a generator can start up, warm up, and transfer switch does its job.
Even if a bunch of servers don't have any UPS or battery backup because they're designed to tolerate individual node (or whole rack, or whole row failures) the core network equipment in a datacenter will still have a huge battery plant.
Ideally if you have a chilled water loop for cooling you do not want it anywhere near your big-ass racks of batteries. Or near the racks that contain the rectifiers and DC breakers, distribution bus bars.
If you look at the battery racks in a traditional telco CO in the US for instance you will see that all of the cabling and batteries are a minimum of 1 foot off the floor, so that the whole place could theoretically flood and the DC distribution would remain unaffected. Same principle that applies to very traditional setups with wet-cell 2V lead acid batteries also applies to more modern things if building from scratch.