Al wire is used a lot more than most people think. Here's the big differences between Al and Cu wire.
Cu is more conductive than Al so an Al wire has to have a cross section area about 1.56 times that of a Cu with the same current capacity.
But Cu is also denser than Al so the Al wire is only about 0.47 times the weight of the Cu wire.
Al is is much cheaper than Cu so the Al wire is only about 13% the cost of the Cu wire.