As near to 100% as makes no difference every single house is already wired for 240v. In fact wired for it and using it: electric ranges, stoves, dryers, etc are all 240v.
NEMA even defines 240v receptacles/plugs for normal amperage: NEMA 6-15 (two horizontal blades: meh face) and 6-20 (one vertical, one horizontal: wink with other eye closed). Unlike the common 240v dryer/large appliance cords that are huge and bulky 6-15 and 6-20 are about the same size as our current 120v plugs. They have the same compatibility as 5-15/5-20: The 15 amp version fits in the 20 amp receptacle but the 20 amp only fits 20 amp. And it is impossible to plug 120 into 240 or vice-versa. Everything made for 120v (to a rough approximation) is also rated for 240v.
Unfortunately no one bothers to install the 6-15/6-20 plugs. There is nothing stopping any builder from doing it standard, especially in the kitchen. There is nothing stopping a homeowner/buyer from asking for it either. But no one does. Therefore there is no market for appliances that use these plugs. And thus no demand to wire for them.
It would likely take a push from government, manufacturers, the NEC, etc to push for supporting 240v for common appliances. Start installing them in new homes. Offering the 240v version of electric kettles and such.
Note: some European appliances can be wired up this way and will run fine because they tolerate 60Hz but not all of them.