No, they're two hots with 240V between them, and a neutral, 120V to each hot. No protective ground. See [1]. The neutral is grounded, but usually back at the pole transformer.
Protective ground is never supposed to carry current unless there's a fault. The neutral in a 3-prong dryer plug is the return for the 120V motor, so it carries current.
I've had an open neutral on my house. A tree slowly grew enough to take out the drop to the house, and it broke the neutral first. The computers were fine but smoke came out of the washing machine, which saw overvoltage.
[1] https://epicelectrical.com/3-prong-vs-4-prong-dryer-outlet/